Treon Industrial Node 6 old Default Configuration

Legacy documentation

This page is preserved from the previous knowledge base and describes older Treon products and manual configuration workflows. It is kept for reference and is not maintained against current Treon Connect releases.

This article shows the default configuration of the Treon Industrial Node 6 before FW 6.17Fig.: Treon Industrial Node 6 DM Model.

Timer Parameters

Time ON/OFF Measurement Selection
Timer 1 1h ON 0
Timer 2 6h ON 1
Timer 3 24h OFF 2 and 3
Status Interval 3h ON none

Measurement Parameters

Measurement ID 0 1 2 3 Default
Axis 3 3 3 x-axis All
G-Range 4 4 4 4 4
Sample Amount 36864 36864 36864 68268 110592
Calculations 1 and 3 2 and 4 5 6 0

Calculation Parameters

CalcID 1 2 3 4 5 6 Default
Features v-RMS, v-PEAK, v-P2P, Clipping detect LOW FFT, Clipping detect a-RMS, a-PEAK, a-P2P, Kurtosis, Crest, Clipping detect HIGH FFT, Clipping detect Raw data Raw data FFT, aRMS, aPEAK
Low cut-off 10 10 no filter no filter no filter
High cut-off 1000 1333 no filter no filter no filter
Decimation 9 0 1
Averages 0 9 0
Overlap % 0 0 0
Window Hanning Hanning Hanning
Lines of resolution 1600 1600 2048
FFT format Variable Variable Auto (no variable)

Wakeup Parameters

Default
Feature Enable OFF
Wake-up G-range 4G
Wake-up threshold 8
Wake-up Action Delay 30s
Wake-up Blank-time 900s
Action measurement ON
Action Indication OFF
Action LED ON
Measurements to be triggered 1