This article shows the default configuration of the Treon Industrial Node 6.
Fig.: Treon Industrial Node 6 DM Model. Timer Parameters Time ON/OFF Measurement Selection Timer 1 1h ON 0 Timer 2 6h ON 1 Timer 3 24h OFF 2 and 3 Status Interval 3h ON none Measurement Parameters Measurement ID 0 1 2 3 Default Axis 3 3 3 x-axis All G-Range 4 4 4 4 4 Sample Amount 36864 36864 36864 68268 110592 Calculations 1 and 3 2 and 4 5 6 0 Calculation Parameters CalcID 1 2 3 4 5 6 Default Features v-RMS, v-PEAK, v-P2P, Clipping detect LOW FFT, Clipping detect a-RMS, a-PEAK, a-P2P, Kurtosis, Crest, Clipping detect HIGH FFT, Clipping detect Raw data Raw data FFT, aRMS, aPEAK Low cut-off 10 10 no filter no filter no filter High cut-off 1000 1333 no filter no filter no filter Decimation 9 0 1 Averages 0 9 0 Overlap % 0 0 0 Window Hanning Hanning Hanning Lines of resolution 1600 1600 2048 FFT format Variable Variable Auto (no variable) Wakeup Parameters Default Feature Enable OFF Wake-up G-range 4G Wake-up threshold 8 Wake-up Action Delay 30s Wake-up Blank-time 900s Action measurement ON Action Indication OFF Action LED ON Measurements to be triggered 1 Treon Support You still have questions?