Industrial Node 6k

Sep 20, 2022 · 2 minutes to read

Treon Industrial Node 6

Industrial Node 6k default Treon configuration

Timer Parameters

TimeON/OFFMeasurement Selection
Timer 11hON0
Timer 26hON1
Timer 324hOFF2 and 3
Status Interval3hONnone

Measurement Parameters

Measurement ID0123Default
Axis333x-axisAll
G-ramge44444
Sample Amount36864368643686468268110592
Calculations1 and 32 and 4560

Calculation Parameters

CalcID123456Default
Featuresv-RMS, v-PEAK, v-P2P, Clipping detectLOW FFT, Clipping detecta-RMS, a-PEAK, a-P2P, Kurtosis, Crest, Clipping detectHIGH FFT, Clipping detectRaw dataRaw dataFFT, aRMS, aPEAK
Low cut-off1010no filterno filterno filter
High cut-off10001333no filterno filterno filter
Decimation901
Averages090
Overlap %000
WindowHanningHanningHanning
Lines of resolution160016002048
FFT formatVariableVariableAuto (no variable)

Wakeup Parameters

Default
Feature EnableOFFOFF
Wake-up G-range4G4G
Wake-up threshold28
Wake-up Action Delay5s30s
Wake-up Blank-time3600s900s
Action measurementONON
Action IndicationONOFF
Action LEDOFFON
Measurements to be triggered11

 


Was this article helpful? Let us know.